• DocumentCode
    759642
  • Title

    A busbar differential protection relay suitable for use with measurement type current transformers

  • Author

    Kang, Yong-Cheol ; Lim, Ui-Jai ; Kang, Sang-Hee ; Crossley, Peter A.

  • Author_Institution
    Div. of Electron. & Inf. Eng., Chonbuk Nat. Univ., Chonju, South Korea
  • Volume
    20
  • Issue
    2
  • fYear
    2005
  • fDate
    4/1/2005 12:00:00 AM
  • Firstpage
    1291
  • Lastpage
    1298
  • Abstract
    The design, evaluation and implementation of a busbar current differential protection relay suitable for use with measurement type current transformers (CTs) is described in the paper. The relay operates in conjunction with a saturation detection algorithm, which effectively detects the start and end of each saturation period using a technique based on the third-difference function applied to the current signal. A blocking signal is activated immediately after the onset of saturation and is maintained active until the saturation period plus an additional delay of one cycle has expired. For internal faults that result in CT saturation, the relay issues a trip command before the blocking signal is activated. For external faults, that result in CT saturation, the blocking signal arrives first and the trip command remains inactive. Test results indicate that the relay successfully discriminates between internal and external faults, even when the remanent flux in a CT is high and the fault capabilities of the measurement CTs are severely limited. The paper concludes by describing how the relay was implemented on a prototype relay based on a digital signal processor. Compared to a conventional busbar differential protection scheme, the new relay achieves greater stability on external faults and enhanced sensitivity for internal faults.
  • Keywords
    busbars; current transformers; power system faults; relay protection; blocking signal; busbar differential protection relay; digital signal processor; external faults; internal faults; measurement type current transformers; remanent flux; saturation detection algorithm; third-difference function; Added delay; Circuit faults; Current measurement; Current transformers; Detection algorithms; Digital relays; Fault currents; Protection; Protective relaying; Testing; Blocking signal and remanent flux; busbar protection; current transformer saturation; difference function; measurement CT;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.834325
  • Filename
    1413392