DocumentCode
760155
Title
Voltage tolerance testing of three-phase voltage source converters
Author
Sannino, Ambra ; Bollen, Math H J ; Svensson, Jan
Author_Institution
Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
Volume
20
Issue
2
fYear
2005
fDate
4/1/2005 12:00:00 AM
Firstpage
1633
Lastpage
1639
Abstract
This paper proposes a protocol for testing the immunity of three-phase self-commutated converters to voltage dips. An overview of voltage dips due to short circuits and earth faults that may affect a converter is given and their effect on the converter is demonstrated through simulation. Results confirm that the existing standard protocol given in IEC 61000-4-11 is not complete. An extended testing protocol is therefore proposed, which is compatible with IEC 61000-4-11.
Keywords
AC machines; immunity testing; power system faults; voltage dividers; IEC 61000-4-11; earth faults; immunity; short circuits; three-phase self-commutated converters; three-phase voltage source converters; voltage dips; voltage tolerance testing; Circuit testing; Converters; IEC standards; Immunity testing; Power conversion; Power quality; Power system stability; Protocols; Variable speed drives; Voltage fluctuations; EMC; immunity; power electronics; power quality; voltage dip (voltage sag);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.833881
Filename
1413436
Link To Document