DocumentCode
760726
Title
Research of Impedance Characteristics for Medium-Voltage Power Networks
Author
Xiaoxian, Yang ; Tao, Zheng ; BaoHui, Zhang ; Fengchun, Ye ; Jiandong, Duan ; Minghui, Shi
Author_Institution
Sch. of Electr. Eng., Xi´´an Jiaotong Univ.
Volume
22
Issue
2
fYear
2007
fDate
4/1/2007 12:00:00 AM
Firstpage
870
Lastpage
878
Abstract
The general method to investigate the impedance characteristics with a network analyzer is discussed. The common properties of the impedance are studied based on two-months observation of two 10-kV medium-voltage power networks. Meanwhile, the difference of the impedance measured at the headside and tailside of a feeder, the impedance characteristic impacted by the operating mode of the power system, the time variance of the impedance, and the characteristic obtained from a different coupling mode are also studied carefully. The results show that the characteristic impedance is in correlation with the power system structure and its configurations, and its value is about several tenths of ohms. The input impedance varies scarcely with the time. The capacitor group connected to the bus has no influence on the input impedance. And the input impedances in common mode and differential mode are both symmetric. The impedance value in differential-mode coupling is higher than that in common-mode coupling
Keywords
distribution networks; electric impedance; 10 kV; capacitor; common mode coupling; differential mode coupling; feeder; impedance characteristics; medium voltage power networks; network analyzer; Conductors; Impedance measurement; Instruments; Medium voltage; Power cables; Power measurement; Power system analysis computing; Substations; Testing; Time measurement; Impedance characteristic; medium-voltage (MV) distribution network; power-line communications;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.881573
Filename
4141178
Link To Document