• DocumentCode
    781983
  • Title

    Thyristor controlled ground fault current limiting system for ungrounded power distribution systems

  • Author

    Sugimoto, S. ; Neo, S. ; Arita, H. ; Kida, J. ; Matsui, Y. ; Yamagiwa, T.

  • Author_Institution
    Electr. Power Res. & Dev. Center, Chubu Electr. Power Co. Inc., Nagoya, Japan
  • Volume
    11
  • Issue
    2
  • fYear
    1996
  • fDate
    4/1/1996 12:00:00 AM
  • Firstpage
    940
  • Lastpage
    945
  • Abstract
    A thyristor controlled ground fault current limiting system (TGCL) was proposed to prevent one-line ground fault current rises due to increased capacitance to ground. Basic components of the TGCL are a main ground fault current limiter, which rapidly adjusts a compensating reactor level for the capacitance to ground, and the TGCL´s controller. Control is ensured by an in-phase control method for zero-phase sequence voltage and current. The method determines the direction of ground faults and the compensating reactor level. The fast control which can be realized shows the TGCL is a valuable protecting system for high ground fault current distribution systems
  • Keywords
    current limiters; distribution networks; overcurrent protection; power system control; power system protection; thyristor applications; capacitance to ground; compensating reactor level; in-phase control method; one-line ground fault current rises; thyristor controlled ground fault current limiting system; ungrounded power distribution systems; zero-phase sequence current; zero-phase sequence voltage; Capacitance; Circuit faults; Control systems; Fault current limiters; Fault currents; Inductors; Power distribution; Power system reliability; Protection; Substations; Thyristors; Transformers; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.489355
  • Filename