DocumentCode :
783817
Title :
Breakdown Voltage of Conditioned 24 kV-Vacuum Tubes as a Function of Ramp Rate
Author :
König, D. ; Schmidt, H.
Author_Institution :
Technical University of Darmstadt, High Voltage Laboratory, Darmstadt, Germany
Issue :
4
fYear :
1985
Firstpage :
715
Lastpage :
720
Abstract :
For the determination of the dielectric strength of different factory-made vacuum interrupter tubes, in the short time range, the breakdown voltage was measured as a function of the voltage ramp rate for various contact distances by applying linear rising impulse voltage with a steepness from 1 kV/ ¿s up to 3 MV/ ¿s. Preconditioning of the contacts was performed with a series of impulse breakdowns. An impulse voltage measuring circuit with a damped capacitive voltage divider and damped lead-in wire was used for the investigations. Adequate steps were taken to avoid flashovers outside the tubes and to give protection against X-rays. After preconditioning, g, some vacuum tubes reached a maximum dielectric strength of 550 kV at the rated contact distance of 14 mm. The minimum values were about 120 kV. The shape of the voltage ramp curves, which is dependent on the contact distance, leads to a conclusion on the effective breakdown mechanisms.
Keywords :
Breakdown voltage; Circuits; Dielectric breakdown; Dielectric measurements; Electric breakdown; Electron tubes; Interrupters; Time measurement; Vacuum breakdown; Voltage measurement;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/TEI.1985.348894