Charge comparison protection of transmission lines-relaying concepts
Author
Ernst, Leonard J. ; Hinman, Walter L. ; Quam, David H. ; Thorp, James S.
Author_Institution
Dowty Control Technologies, Boonton, NJ, USA
Volume
7
Issue
4
fYear
1992
fDate
10/1/1992 12:00:00 AM
Firstpage
1834
Lastpage
1852
Abstract
The authors describe the relaying concepts of charge comparison. Charge comparison is a new transmission line protection system. It is a form of current differential relaying. Charge comparison largely resolves the traditional problems of current differential relaying of transmission lines, which are that protection is lost if a channel fails, a large channel capacity is required, and precise channel delay compensation is required. This technique is suitable for the protection of two- or three-terminal AC transmission lines, of all lengths and voltage levels, with or without series of shunt compensation, with three-hole or single-pole tripping
Keywords
power system protection; power transmission lines; relay protection; channel delay compensation; charge comparison protection; current differential relaying; relaying; shunt compensation; single-pole tripping; three-pole tripping; three-terminal AC transmission lines; transmission lines; two-terminal lines; Channel capacity; Control systems; Delay; Digital relays; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Voltage transformers; Writing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.156986
Filename
156986
Link To Document