• DocumentCode
    796985
  • Title

    Voltage compensation of an induction generator with long-shunt connection

  • Author

    Bim, E. ; Szajner, J. ; Burian, Y.

  • Author_Institution
    Electr. Eng. Fac., UNICAMP, Sao Paulo, Brazil
  • Volume
    4
  • Issue
    3
  • fYear
    1989
  • fDate
    9/1/1989 12:00:00 AM
  • Firstpage
    526
  • Lastpage
    530
  • Abstract
    Preliminary studies of voltage vs. speed relationships, stability of generated voltage, and voltage compensation of the self-excited induction generator are presented. In order to improve the voltage regulation, the long-shunt connection of the capacitors to the generator is used. The magnetizing inductance of the machine is used as a saturable reactor. The values of the capacitors for series and parallel connections are obtained from the saturation characteristics of the machine. Experimental results are reported. The maximum voltage drop is about 4%
  • Keywords
    asynchronous generators; compensation; capacitors; generated voltage stability; induction generator; long-shunt connection; magnetizing inductance; saturable reactor; self-excited; voltage compensation; voltage drop; voltage regulation; Capacitors; Frequency; Inductance; Induction generators; Magnetic flux; Rotors; Saturation magnetization; Stator cores; Steady-state; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.43258
  • Filename
    43258