DocumentCode
797097
Title
An adaptive distance relay and its performance comparison with a fixed data window distance relay
Author
Sidhu, Tarlochan S. ; Ghotra, Daljit S. ; Sachdev, Mohindar S.
Author_Institution
Univ. of Western Ontario, London, Ont., Canada
Volume
17
Issue
3
fYear
2002
fDate
7/1/2002 12:00:00 AM
Firstpage
691
Lastpage
697
Abstract
This paper describes the design, implementation and testing of an adaptive distance relay. The relay uses a fault detector to determine the inception of a fault and then uses data windows of appropriate length for estimating phasors and seen impedances. Hardware and software of the proposed adaptive relay are also described in this paper. The relay was tested using a model power system and a real-time playback simulator. Performance of the relay was compared with a fixed data window distance relay. Some results are reported in this paper. These results indicate that the adaptive distance relay provides faster tripping in comparison to the fixed data window distance relay.
Keywords
power system analysis computing; power system protection; power system relaying; relay protection; computer simulation; data windows; fault inception detector; impedances estimation; model power system; performance comparison; phasors estimation; power system adaptive distance relay; real-time playback simulator; Electrical fault detection; Hardware; Impedance; Power system faults; Power system modeling; Power system relaying; Power system simulation; Protective relaying; Real time systems; System testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.1022788