• DocumentCode
    797097
  • Title

    An adaptive distance relay and its performance comparison with a fixed data window distance relay

  • Author

    Sidhu, Tarlochan S. ; Ghotra, Daljit S. ; Sachdev, Mohindar S.

  • Author_Institution
    Univ. of Western Ontario, London, Ont., Canada
  • Volume
    17
  • Issue
    3
  • fYear
    2002
  • fDate
    7/1/2002 12:00:00 AM
  • Firstpage
    691
  • Lastpage
    697
  • Abstract
    This paper describes the design, implementation and testing of an adaptive distance relay. The relay uses a fault detector to determine the inception of a fault and then uses data windows of appropriate length for estimating phasors and seen impedances. Hardware and software of the proposed adaptive relay are also described in this paper. The relay was tested using a model power system and a real-time playback simulator. Performance of the relay was compared with a fixed data window distance relay. Some results are reported in this paper. These results indicate that the adaptive distance relay provides faster tripping in comparison to the fixed data window distance relay.
  • Keywords
    power system analysis computing; power system protection; power system relaying; relay protection; computer simulation; data windows; fault inception detector; impedances estimation; model power system; performance comparison; phasors estimation; power system adaptive distance relay; real-time playback simulator; Electrical fault detection; Hardware; Impedance; Power system faults; Power system modeling; Power system relaying; Power system simulation; Protective relaying; Real time systems; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2002.1022788
  • Filename
    1022788