Voltage recovery after unbalanced and balanced voltage dips in three-phase systems
Author :
Bollen, Math H J
Author_Institution :
Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
Volume :
18
Issue :
4
fYear :
2003
Firstpage :
1376
Lastpage :
1381
Abstract :
This paper studies the recovery of the voltage after a voltage dip due to a fault in a three-phase system. The instant of voltage recovery corresponds to the instant of fault clearing. For single-phase and phase-to-phase faults, a single point-on-wave of voltage recovery can be defined. For two-phase-to-ground and three-phase faults, the recovery takes place in two or three steps. The voltage recovery is described in a systematic way by using a classification of three-phase unbalanced voltage dips. The voltage recovery needs to be modeled correctly for studies of equipment immunity against voltage dips.
Keywords :
power distribution; power supply quality; power system faults; power transmission; equipment immunity; power distribution; power quality; power transmission; solidly-grounded systems; three-phase faults; three-phase system; two-phase-to-ground faults; unbalanced voltage dips; voltage recovery; voltage sags; Circuit faults; Electronics packaging; Power quality; Power system faults; Power system modeling; Power system simulation; Power transmission; Shape measurement; Surges; Voltage fluctuations;