  • Abstract
    In this letter, the effects of line compensation of an single-machine infinite-bus power system using fixed-capacitor thyristor-controlled reactor-type or SVC for transient stability enhancement are analyzed. In particular, a novel method for analysis of line compensation by an SVC is presented. The maximum power transfer, for line compensation by FACTS controllers can be written in the form=(1-k) where is the maximum power transfer for the uncompensated line and k is the degree of compensation. The analysis revealed that the effectiveness of the SVC for stability enhancement is increased if the degree of compensation of the line is increased.
  • Keywords
    compensation; control system analysis; flexible AC transmission systems; power capacitors; power system control; power system stability; power system transients; static VAr compensators; thyristor convertors; FACTS controller; SVC; control simulation; fixed-capacitor thyristor-controlled reactors; line compensation; maximum power transfer; power system transient stability enhancement; single-machine infinite-bus power system; Control systems; Guidelines; Power & Energy Society; Power capacitors; Power system analysis computing; Power system stability; Power system transients; Power systems; Static VAr compensators; Thyristors;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.1998.1236741
  • Filename
    1236741