DocumentCode :
804416
Title :
A Topology Error Identification Method Directly Based on Collinearity Tests
Author :
Lourenço, Elizete M. ; Costa, Antonio J A Simões ; Clements, Kevin A. ; Cernev, Rafael A.
Author_Institution :
Univ. Fed. do Parana, Curitiba
Volume :
21
Issue :
4
fYear :
2006
Firstpage :
1920
Lastpage :
1929
Abstract :
A method for topology error identification based on collinearity tests involving Lagrange multipliers and the columns of the corresponding covariance matrix is presented. It relies on a geometric interpretation of the multipliers associated with the equality constraints that model circuit breaker status in generalized state estimation. The method is conceptually simple, and its implementation requires little computational effort, therefore being suitable for real-time applications. Results of several simulated cases conducted at the substation level on a real-life test system based on a subnetwork of the Brazilian Northern power system are used to illustrate the performance of the proposed technique
Keywords :
circuit breakers; covariance matrices; power system state estimation; Brazilian Northern power system; Lagrange multipliers; circuit breaker; collinearity tests; covariance matrix; geometric interpretation; real-life test system; topology error identification method; Circuit breakers; Circuit testing; Circuit topology; Computational modeling; Covariance matrix; Lagrangian functions; Power system modeling; Power system simulation; Solid modeling; State estimation; Bad data analysis; power system real-time operation; power system state estimation;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2006.881113
Filename :
1717597
Link To Document :
بازگشت