    A Model to Extract Wind Influence From Outdoor IR Thermal Inspections

  • Author

    Bortoni, E.C. ; Santos, Leonardo ; Bastos, G.S.

  • Author_Institution
    Itajuba Fed. Univ., Itajuba, Brazil
  • Volume
    28
  • Issue
    3
  • fYear
    2013
  • fDate
    Jul-13
  • Firstpage
    1969
  • Lastpage
    1970
  • Abstract
    A model proposal to determine the influence of wind over temperature measurements when conducting outdoor infrared (IR) themographic inspections is addressed in this paper. A wind velocity-dependent temperature reduction factor is developed and applied in order to estimate the target temperature in the absence of wind, which is considered as the worst case. The model makes use of only two unknown coefficients that are determined for each application. The proposed model is applied and compared to data available in the technical literature.
  • Keywords
    environmental factors; infrared imaging; inspection; substations; temperature measurement; HV substation; conducting outdoor infrared themographic inspections; outdoor IR thermal inspections; outdoor high-voltage substations; target temperature estimation; temperature measurements; wind influence extraction; wind velocity-dependent temperature reduction factor; Data models; Heating; Inspection; Mathematical model; Temperature; Temperature measurement; Wind speed; Environmental factors; infrared (IR) imaging; outdoor high-voltage (HV) substations; preventive maintenance;