DocumentCode
815604
Title
Testing of active current balance in parallel thyristor bridges
Author
Gibbs, Irving A.
Author_Institution
Eaton Corp., Arden, NC, USA
Volume
20
Issue
2
fYear
2005
fDate
6/1/2005 12:00:00 AM
Firstpage
481
Lastpage
484
Abstract
Test results of active current balance (ACB) at Georgia Power´s McDonough Plant show the effect of ACB applied to parallel thyristor bridges in generator excitation applications. This paper presents test results of ACB, a new technique that adjusts the average current in parallel leg thyristors to facilitate current balance between the parallel operating bridges. The unbalance between parallel thyristors is typically caused by differences in inductance feeding the thyristors and by the conducting characteristics of the thyristors. Balance is accomplished by periodically inhibiting the firing of thyristors that carry more than the average current. The thyristors that are conducting carry more current during this interval and their average current is increased. Test results show that the current balance between the parallel operating thyristors in the bridges is significantly improved when ACB is enabled. The results of rapid changes in load while ACB is enabled are also shown.
Keywords
bridge circuits; power plants; steam turbines; thyristor applications; turbogenerators; Georgia Power McDonough Plant; active current balance; generator excitation application; parallel leg thyristor; parallel thyristor bridge; Bridge circuits; Fires; Inductance; Leg; Power generation; Rectifiers; Regulators; Software testing; System testing; Thyristors; AC generator excitation; digital systems; drives; rectifiers; silicon-controlled rectifier; synchronous machine exciter applications; testing; thyristor;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.2004.837280
Filename