• DocumentCode
    821829
  • Title

    Improved contingency measures for operation and planning applications

  • Author

    Schlueter, R.A. ; Sekerke, J.E. ; Burnett, K.L. ; Costi, A.G.

  • Author_Institution
    Michigan State Univ., East Lansing, MI, USA
  • Volume
    4
  • Issue
    4
  • fYear
    1989
  • fDate
    11/1/1989 12:00:00 AM
  • Firstpage
    1430
  • Lastpage
    1437
  • Abstract
    Three new contingency measures are proposed and tested based on a large power system peak load base case. The Type II contingency measure is zero for all noncritical contingencies, has no misclassification or false alarm problems, and ranks contingencies according to their largest thermal limit violation. It should be used when operating conditions are known exactly. The Type III contingency measure has very small or zero contingency measure for noncritical contingencies, has no perceptible misclassification or false alarm problems, and appears to rank contingencies by their worst thermal limit violation. The Type III contingency measure is very useful for selecting contingencies where the precise operating conditions are unknown. A Type IV contingency measure sets branch weights to zero on all branches that do not experience thermal overloads for a set of contingencies. The Type IV contingency measure is useful for selecting single contingencies that when taken in combination could produce critical multiple contingencies
  • Keywords
    power system planning; Type II contingency measure; Type III contingency measure; Type IV contingency measure; contingency measures; operation; planning; power system peak load; worst thermal limit violation; Packaging; Particle measurements; Performance evaluation; Power system planning; Production; Security; Software packages; System testing; Voltage; Weight measurement;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.41694
  • Filename
    41694