• DocumentCode
    830429
  • Title

    Analysis of HVDC converters connected to weak AC systems

  • Author

    Frankén, B. ; Andersson, G.

  • Author_Institution
    Dept. of Electr. Power Syst., R. Inst. of Technol., Stockholm, Sweden
  • Volume
    5
  • Issue
    1
  • fYear
    1990
  • fDate
    2/1/1990 12:00:00 AM
  • Firstpage
    235
  • Lastpage
    242
  • Abstract
    A method of analysis is presented and applied to a model system which is well established and extensively used in studies of HVDC converters connected to weak AC systems. The method is based on fundamental frequency quantities. A variety of phenomena and interactions of the AC/DC system can be analyzed, and basic understanding of the mechanisms can be gained. Some important properties of the system, such as voltage/power stability in different control modes and stability of tap changer action, are analyzed. Furthermore, they dynamics of a system consisting of a static VAr compensator (SVC) and DC converters are analyzed, and the requirements for stable operation are derived within the framework of the method of analysis presented. These results are verified by time simulation done by a transient stability program
  • Keywords
    DC power transmission; power convertors; power systems; stability; AC/DC system; HVDC converters; control; power stability; static VAr compensator; tap changer action; time simulation; transient stability program; voltage stability; weak AC systems; Control systems; Costs; HVDC transmission; Inverters; Power system modeling; Sensitivity analysis; Stability analysis; Static VAr compensators; Thyristors; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.49111
  • Filename
    49111