• DocumentCode
    839352
  • Title

    Interleaved High-Voltage Transformer Windings

  • Author

    van Nuys, R.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    5
  • fYear
    1978
  • Firstpage
    1946
  • Lastpage
    1954
  • Abstract
    Interleaved-turn high-voltage transformer windings are a useful alternative to continuous disc and layer windings for a wide range of transformer output and voltage ratings. Many configurations have been devised to meet different requirements. This paper reports the discovery that the original and most- commonly-used form of interleaved winding has an unexpectedly large internal oscillatory response to chopped-wave or front-of-wave impulse (lightning surge) voltages. It describes the subsequent development of a less-oscillatory winding which allows smaller insulation clearances for equivalent reliability.
  • Keywords
    Costs; Interleaved codes; Lightning; Oil insulation; Power transformer insulation; Power transformers; Transformer cores; Voltage; Voltage-controlled oscillators; Windings;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1978.354691
  • Filename
    4181639