84094
Title
Traditional Time - Current Curves Are Not Enough, Adding
Considerations
Author
Papallo, Thomas ; Valdes, Marcelo E.
Author_Institution
GE Energy Ind. Solutions, Plainville, CT, USA
Volume
49
Issue
1
fYear
2013
fDate
Jan.-Feb. 2013
Firstpage
264
Lastpage
274
Abstract
Overcurrent device selectivity has always been desirable in power distribution systems. Recent changes in the U.S. National Electrical Code (NFPA 70-2005 and subsequent) have increased the demand for near perfect selectivity. Simultaneously, heightened sensitivity to the effect of slow clearing times on arc flash hazard has increased the need for fast and sensitive overcurrent protection, particularly at the larger upper tier overcurrent devices. When the selectivity solution is to oversize or to slow down protection at midlevel feeders above the branch circuit breakers (CBs), arc-flash-incident energy at higher levels in systems can reach unacceptable levels. Optimized protection and selectivity may be achieved by optimizing instantaneous settings and algorithms in upstream protectors. Such selectivity may be accomplished primarily by understanding the current-limiting behavior of the downstream protective device and understanding the thermal capacitance needed to melt upstream fuse elements or intentional damping added to upstream CB trip units. When CBs trip in subcycle times and clearing times are instantaneous, traditional time-current curves (TCCs) are insufficient to correctly demonstrate device operation. The authors will describe two graphical representations based on the I2t let-through of the downstream device and I2t requirement to trip the upstream device. The I2t representations more effectively describe protective device behavior in the instantaneous region below 0.010 s normally excluded in traditional TCCs. Furthermore, a technique, a theoretical basis, and a proposed test protocol that are suitable for a wide range of devices will be presented.
Keywords
arcs (electric); circuit breakers; current limiters; overcurrent protection; power distribution; I2t considerations; NFPA 70-2005; U.S. National Electrical Code; arc flash hazard; arc-flash-incident energy; branch circuit breakers; current-limiting behavior; downstream protective device; graphical representations; intentional damping; melt upstream fuse elements; midlevel feeders; overcurrent device selectivity; overcurrent protection; power distribution systems; thermal capacitance; traditional time-current curves; upstream protectors; Arc discharges; Circuit breakers; Circuit faults; Fault currents; Fuses; Limiting; Visualization; Arc flash protection; current-limiting circuit breakers (CBs); current-limiting fuses; selectivity;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2012.2231659
Filename
6374245
Link To Document