DocumentCode :
843083
Title :
Mutual coupling between finite lengths of parallel or angled horizontal earth return conductors
Author :
Rogers, Eldon J. ; White, John F.
Author_Institution :
Bonneville Power Adm., Vancouver, WA, USA
Volume :
4
Issue :
1
fYear :
1989
Firstpage :
103
Lastpage :
113
Abstract :
Mutual coupling between earth return current and potential test conductors used during stage tests of a grounding system is discussed. The coupling is a source of significant error in measuring grounding potential and grounding system impedance. Mutual impedance formulae are presented for correcting mutual coupling errors resulting from any length of paralleled or angled horizontal ground return current and potential conductors. The formulae are an extension of the complex image plane approximation of J.R. Carson´s (1926) formula for infinitely long parallel conductors.<>
Keywords :
earthing; power system measurement; power system protection; complex image plane approximation; earth return conductors; grounding system; impedance; mutual coupling; potential test; power system measurement; power system protection; Conductors; Current measurement; Earth; Equations; Frequency; Grounding; Impedance; Mutual coupling; Power engineering and energy; System testing;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19196
Filename :
19196
Link To Document :
بازگشت