    Application of air-break switches for de-energizing transmission lines

  • Author

    Patel, S.G. ; Holcombe, W.F., Jr. ; Parr, D.E.

  • Author_Institution
    Georgia Power Co., Atlanta, GA, USA
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    368
  • Lastpage
    374
  • Abstract
    Results of an extensive evaluation and recommendations are presented for the application of air-break switches equipped with fast interrupting mechanical devices for line dropping on a 115 kV system. A computer study as well as field tests indicated that parallel lines have negligible effect on charging current. However, the current is affected significantly by conductor configurations. It was also found that high tip speed and minimum bounce of quick-break devices significantly increase the charging current interruption capability
  • Keywords
    air blast circuit breakers; power transmission lines; 115 kV; air-break switches; charging current interruption capability; computer study; conductor configurations; fast interrupting mechanical devices; transmission line de-energisation; Circuit testing; Conductors; Current measurement; Guidelines; Insulation; Multiconductor transmission lines; Power transmission lines; Substations; Switches; Transmission lines;