DocumentCode
849265
Title
Preliminary qualification of a HPOF pipe cable system for service at 765 kv
Author
Engelhardt, J.S. ; Blodgett, R.B.
Author_Institution
The Anaconda Company, Greenwich, Connecticut
Volume
94
Issue
5
fYear
1975
Firstpage
1569
Lastpage
1583
Abstract
Tan δ (dissipation factor)data on Cable System B is updated to include the full 2-year 500/550 kV test program at Waltz Mill and the 10-month 765/800 kV extended test program. This data is analyzed, demonstrating no change with time of tan δ for the system. Particular attention is paid to the paper splice, which exhibits a thermoelectric stability limitation at the 765/800 kV level. The outstanding performance of the PP/C splice is emphasized. Consideration of the operation of a very highly stressed oil impregnated paper insulation HPOF pipe system at 765 kV is suggested, including potential single circuit transmission capacity calculations.
Keywords
Automatic testing; Communication cables; Conductors; Cooling; Oil insulation; Petroleum; Qualifications; System testing; Temperature; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31998
Filename
1601600
Link To Document