DocumentCode :
849575
Title :
Measurement of fluid flow resistance for forced cooled underground transmission lines
Author :
Slutz, R. ; Glicksman, L.R. ; Rohsenow, W.M. ; Buckweitz, M.
Author_Institution :
Massachusetts Institute of Technology, Cambridge, Mass.
Volume :
94
Issue :
5
fYear :
1975
Firstpage :
1831
Lastpage :
1834
Abstract :
Isothermal tests of a pipe type cable system were made in both the laminar and turbulent flow regimes. Transition to turbulent flow occurs at much lower Reynolds number than for bare pipes. The flow resistence is strongly influenced by skid wire geometry in the turbulent region and by cable configuration in the laminar region. Previous theoretical predictions for flow resistence in the laminar region are in error by twenty percent.
Keywords :
Electrical resistance measurement; Fluid flow; Fluid flow measurement; Force measurement; Isothermal processes; Power cables; System testing; Transmission line measurements; Transmission line theory; Wire;