Abstract
The results are reported of a project designed to reduce the magnitude of transient high-frequency electromagnetic field disturbances near 230-kV line disconnect switches by structural shielding. A reduction in peak transient electric fields from 600 volts per meter to an equipment specification value of 1 volt per meter at the site of a large computer installation has been obtained. The transient field waveforms and measurement methods are described.
Keywords
Control systems; Electromagnetic fields; Electromagnetic measurements; Electromagnetic shielding; Electromagnetic transients; Magnetic field measurement; Power system transients; Power systems; Substations; Switches;