DocumentCode
852268
Title
Arc extinction performance of SF6 gas blast interrupter
Author
Nishikawa, H. ; Kobayashi, A. ; Okazaki, T. ; Yamashita, S.
Author_Institution
Tokyo Shibaura Electric Company Limited, Kawasaki, Japan
Volume
95
Issue
6
fYear
1976
Firstpage
1834
Lastpage
1844
Abstract
With a model SF6 gas blast interrupter, arc extinction performance was investigated. The measurements were carried out for di/dt values ranging from 13 ∼ 27 A/µs, for RRRV extending from 3.5∼ 13.0kV/µs and for a fixed pressure of 15kg/cm2. On the other hand, the voltage and current wave forms near current zero in the short line fault (SLF) test circuit were calculated employing Mayr´s equation and the interrupting capability was investigated using the arc time constant and arc voltage obtained from the experimental results. From this calculation, the following relation was found. RRRVc ∞ (i)-(2.2∼2.45). The theoretical calculation was found to coincide satisfactorily with the experiments.
Keywords
Circuit testing; Contacts; Current measurement; Frequency; Insulator testing; Interrupters; Oscilloscopes; Switches; Valves; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1976.32284
Filename
1601886
Link To Document