• DocumentCode
    852532
  • Title

    PSS tuning at the Virginia Electric and Power Co. Bath County pumped storage plant

  • Author

    Bollinger, K.E. ; Mistr, A.F., Jr.

  • Author_Institution
    Dept. of Electr. Eng., Alberta Univ., Edmonton, Alta., Canada
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    5/1/1989 12:00:00 AM
  • Firstpage
    566
  • Lastpage
    574
  • Abstract
    An outline is presented of test procedures and results for tuning the power system stabilizers (PSSs) at the Virginia Electric and Power Company Bath County pumped storage plant. High machine reactance and critical operating conditions provided a challenging damping problem that was solved using computerized test equipment and classical feedback controller design techniques. Onsite tests involved obtaining frequency-response data for use in determining PSS parameters. Step responses using a general-purpose digital controller indicated a definite improvement in rotor damping. This same damping was obtained when the original analog PSSs were modified and put into service
  • Keywords
    controllers; damping; electric generators; power system control; pumped-storage power stations; rotors; PSS parameters; Virginia Electric and Power Co. Bath County pumped storage plant; computerized test equipment; critical operating conditions; frequency-response data; machine reactance; power system stabilizers; rotor damping; Damping; Frequency; Power generation; Power system transients; Power systems; Pumps; Samarium; System testing; Test equipment; Tuning;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.193831
  • Filename
    193831