DocumentCode :
852698
Title :
Characteristics of a 40 kVA three phase superconducting transformer and its parallel operation with a conventional transformer
Author :
Ise, T. ; Marutani, Y. ; Murakami, Y. ; Yoneda, E. ; Sugawara, R.
Author_Institution :
Dept. of Electr. Eng., Osaka Univ., Japan
Volume :
5
Issue :
2
fYear :
1995
fDate :
6/1/1995 12:00:00 AM
Firstpage :
941
Lastpage :
944
Abstract :
A 40 kVA three phase superconducting transformer has been developed and tested. From the test results, excellent voltage regulation of 0.3% with a pure resistive load was obtained. For application in a power system, parallel operation with a conventional power transformer using copper windings has been carried out. Although a superconducting transformer cannot continue to operate in case of quenching, the proposed parallel system can overcome the drawback and give an additional fault current limiting function.<>
Keywords :
load (electric); power transformer testing; superconducting coils; superconducting magnets; transformer windings; 40 kVA; application; characteristics; copper windings; fault current limiting; parallel operation; power system; power transformer; pure resistive load; quenching; testing; three phase superconducting transformer; voltage regulation; Copper; Detectors; Fault currents; Phase transformers; Power system faults; Power transformers; Superconducting filaments and wires; Superconducting materials; Switches; Transformer cores;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/77.402704
Filename :
402704
Link To Document :
بازگشت