DocumentCode
852729
Title
A new approach for calculating zone-2 setting of distance relays and its use in an adaptive protection system
Author
Sidhu, Tarlochan S. ; Baltazar, David Sebastian ; Palomino, Ricardo Mota ; Sachdev, Mohindar S.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Western Ontario, London, Ont., Canada
Volume
19
Issue
1
fYear
2004
Firstpage
70
Lastpage
77
Abstract
This paper presents a method for calculating zone-2 setting of distance relays without causing coordination problems. The proposed method is based on the impedance seen by distance relays when faults are simulated on the reach of zone-1 of primary relays for the maximum and minimum generation outputs of the power system. It is shown that the proposed method increases the reach of zone-2 relays without causing coordination problems. The proposed method is modified for use in an adaptive protection system. It is shown that further improvements can be achieved when settings are calculated using the proposed method and the prevailing system conditions. Measures to alleviate the impact of communication failure are discussed. The proposed method and its adaptive version were applied to an existing power system and some results are reported in the paper.
Keywords
power transmission lines; power transmission protection; relay protection; adaptive protection system; backup relay; communication failure; distance relays; online monitoring; power system protection; transmission line protection; zone-2 setting calculation; Adaptive systems; Delay; Digital relays; Impedance; Power generation; Power system faults; Power system protection; Power system relaying; Power system simulation; Protective relaying;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.820202
Filename
1256359
Link To Document