  • Abstract
    This paper presents a method for calculating zone-2 setting of distance relays without causing coordination problems. The proposed method is based on the impedance seen by distance relays when faults are simulated on the reach of zone-1 of primary relays for the maximum and minimum generation outputs of the power system. It is shown that the proposed method increases the reach of zone-2 relays without causing coordination problems. The proposed method is modified for use in an adaptive protection system. It is shown that further improvements can be achieved when settings are calculated using the proposed method and the prevailing system conditions. Measures to alleviate the impact of communication failure are discussed. The proposed method and its adaptive version were applied to an existing power system and some results are reported in the paper.
  • Keywords
    power transmission lines; power transmission protection; relay protection; adaptive protection system; backup relay; communication failure; distance relays; online monitoring; power system protection; transmission line protection; zone-2 setting calculation; Adaptive systems; Delay; Digital relays; Impedance; Power generation; Power system faults; Power system protection; Power system relaying; Power system simulation; Protective relaying;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2003.820202
  • Filename
    1256359