Abstract
In an attempt to generate high pressure with small driving energy, two types of interrupting chamber, two volumes-two pistons-type, and one volume-one piston-type are compared by simulating opening operating characteristics. As the result of the simulations, we concluded that one volume-one piston-type chamber could generate sufficient high pressure and ability to interrupt high current with a simpler structure and limited operating energy. A new GCB for 245-kV GIS adopting the new chamber has been developed.
Keywords
electrical faults; gas blast circuit breakers; interrupters; 245 kV; gas circuit breaker; interrupting chamber; low drive energy; one-volume-one piston-type chamber; operating energy; pressure rise; short line fault; small driving energy; two-volumes-two piston-type chamber; Character generation; Circuit breakers; Circuit faults; Circuit simulation; Fluid flow; Geographic Information Systems; Pistons; Power system faults; Thermal expansion; Valves;