• DocumentCode
    853544
  • Title

    Algorithm comparison for high impedance fault detection based on staged fault test

  • Author

    Huang, Ching-Lien ; Chu, Hui-Yung ; Chen, Ming-Tong

  • Author_Institution
    Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1427
  • Lastpage
    1435
  • Abstract
    Four high-impedance fault-detection algorithms-proportional relaying, ratio ground relaying, second-order harmonic current relaying, and third-order harmonic current relaying-were simulated by mathematical models. Relaying performances using staged fault data were then compared. Results of the fault data processing were used to distinguish the detection characteristics: fault identification, stability, threshold setting adaptability, transient recovery characteristic, and availability. The operations of a ground overcurrent relay and a ratio ground relay were also checked in the test. The results can be used as a reference for the development of a reliable high-impedance fault detector
  • Keywords
    earthing; fault location; power systems; relay protection; availability; fault identification; ground overcurrent relay; high impedance fault detection; proportional relaying; ratio ground relay; ratio ground relaying; second-order harmonic current relaying; stability; staged fault test; third-order harmonic current relaying; threshold setting adaptability; transient recovery characteristic; Electrical fault detection; Fault detection; Impedance; Power system harmonics; Power system relaying; Protection; Protective relaying; Relays; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.193941
  • Filename
    193941