• DocumentCode
    853584
  • Title

    Effect of transmission line loading on the performance characteristics of polyphase distance relay elements

  • Author

    Marttila, R.J.

  • Author_Institution
    Ontario Hydro Res., Toronto, Ont., Canada
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1466
  • Lastpage
    1474
  • Abstract
    The performance characteristics of a polyphase element for the detection of phase faults is examined. The results show the effect of transmission line loading and reach setting on the detection characteristics of forward faults. The polyphase element exhibits tendencies to under-reach for far-end as well as close-in faults with zero fault resistance, under some conditions. The results are presented in a manner that facilitates ready assessment of the expected performance of a polyphase element in a particular application
  • Keywords
    fault location; power transmission lines; relay protection; phase fault detection; polyphase distance relay elements; transmission line loading; Fault detection; Impedance; Phase detection; Power system modeling; Power system relaying; Protection; Protective relaying; Transmission line measurements; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.193945
  • Filename
    193945