Dimensioning of nearby substations interconnected ground system
Author
Sobral, S.T. ; Costa, Vasco S. ; Campos, Marcelo S. ; Goldman, Braulio ; Mukhedkar, D.
Author_Institution
IESA-Int. de Eng. SA, Rio de Janeiro, Brazil
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1604
Lastpage
1614
Abstract
The ground-mat dimensioning of two or more neighboring interconnected substations is treated. A set of calculation procedures, using the decoupled method, is given. It is shown that the electric neighborhood of nearby substations depends on the space constant (or characteristic length) of the ground circuits interconnecting them. A simple procedure is presented for determining the suitable number of aluminium-conductor steel-reinforced ground wire spans near a substation, which are needed to allow a reduction of the ground grid conductor extension
Keywords
earthing; power system protection; substations; decoupled method; earthing; ground system; ground wire; ground-mat dimensioning; power system protection; space constant; substations; Conductors; Distributed parameter circuits; Fault currents; Integrated circuit interconnections; Power cables; Power generation; Power transmission lines; Senior members; Soil; Substations;
fLanguage
English