• DocumentCode
    854034
  • Title

    Operating duty test of surge arresters for HVDC transmission systems

  • Author

    Takanashi, Mitugu ; Yokokura, Tomio ; Maruyama, Seiichi ; Ozawa, Jun ; Shirakawa, Shingo

  • Author_Institution
    Central Research Institute of Electric Power Industry, Tokyo, Japan
  • Volume
    96
  • Issue
    4
  • fYear
    1977
  • fDate
    7/1/1977 12:00:00 AM
  • Firstpage
    1384
  • Lastpage
    1390
  • Abstract
    An operating duty test of a high-voltage (64 kV) dc arrester was performed in the field. The results obtained were compared with those of a laboratory test on a prorated section of thec same arrester (8 kV). This comparison demonstrated the validity of the equivalent prorated test method. In another operating duty test conducted under the severe condition of deblocking with full rectifier voltage against an open inverter end, the operating capabilities of a prorated section were demonstrated.
  • Keywords
    Arresters; Circuit testing; HVDC transmission; Laboratories; Performance evaluation; Rectifiers; Surges; System testing; Thyristors; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1977.32465
  • Filename