DocumentCode
854343
Title
Role of air gaps on AC withstand voltage of an ice-covered insulator string
Author
Farzaneh, M. ; Volat, C. ; Zhang, J.
Author_Institution
Quebec Univ., Chicoutimi, Que.
Volume
13
Issue
6
fYear
2006
fDate
12/1/2006 12:00:00 AM
Firstpage
1350
Lastpage
1357
Abstract
The influence of the number and position of air gaps on the 50% AC withstand voltage, V50, of a short string of 5 IEEE standard insulator units covered with ice was experimentally investigated and numerically simulated. The results show that the V50 is affected by the number and position of the air gaps. The results also show that the presence of a partial arc along the air gap close to the high voltage (HV) electrode leads to a redistribution of the voltage along the ice-covered insulator. Based on the obtained results, suggestions for improving the performance of line insulators under icing conditions were proposed
Keywords
Air gaps; Conductivity; Dielectrics and electrical insulation; Flashover; Ice surface; Numerical simulation; Power engineering and energy; Stress; Voltage; Water heating;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2006.258207
Filename
4027730
Link To Document