• DocumentCode
    854343
  • Title

    Role of air gaps on AC withstand voltage of an ice-covered insulator string

  • Author

    Farzaneh, M. ; Volat, C. ; Zhang, J.

  • Author_Institution
    Quebec Univ., Chicoutimi, Que.
  • Volume
    13
  • Issue
    6
  • fYear
    2006
  • fDate
    12/1/2006 12:00:00 AM
  • Firstpage
    1350
  • Lastpage
    1357
  • Abstract
    The influence of the number and position of air gaps on the 50% AC withstand voltage, V50, of a short string of 5 IEEE standard insulator units covered with ice was experimentally investigated and numerically simulated. The results show that the V50 is affected by the number and position of the air gaps. The results also show that the presence of a partial arc along the air gap close to the high voltage (HV) electrode leads to a redistribution of the voltage along the ice-covered insulator. Based on the obtained results, suggestions for improving the performance of line insulators under icing conditions were proposed
  • Keywords
    Air gaps; Conductivity; Dielectrics and electrical insulation; Flashover; Ice surface; Numerical simulation; Power engineering and energy; Stress; Voltage; Water heating;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2006.258207
  • Filename
    4027730