DocumentCode
862491
Title
A current-based solution for transformer differential protection. II. Relay description and evaluation
Author
Guzmán, Armando ; Zocholl, Stanley ; Benmouyal, Gabriel ; Altuve, Héctor J.
Author_Institution
Schweitzer Eng. Labs., Pullman, WA, USA
Volume
17
Issue
4
fYear
2002
fDate
10/1/2002 12:00:00 AM
Firstpage
886
Lastpage
893
Abstract
For pt.I see ibid., vol.16, p.485-91 (2001). This paper describes a new approach for transformer differential protection that ensures security for external faults, inrush, and overexcitation conditions and provides dependability for internal faults. This approach combines harmonic restraint and blocking methods with a wave-shape recognition technique. We compare in the paper the behavior of some traditional transformer protection methods to that of the new method for real cases of magnetizing inrush conditions.
Keywords
magnetisation; power transformer protection; relay protection; blocking methods; external faults; harmonic restraint; magnetizing inrush conditions; overexcitation conditions; transformer differential protection; transformer protection methods; wave-shape recognition technique; Circuit faults; Fault currents; Magnetic analysis; Power transformers; Protective relaying; Relays; Saturation magnetization; Security; Subspace constraints; Surge protection;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.803736
Filename
1046859
Link To Document