DocumentCode
862610
Title
Diagnostic methods in revealing internal moisture in polymer housed metal oxide surge arresters
Author
Lahti, Kari ; Kannus, Kari ; Nousiainen, Kirsi
Author_Institution
Inst. of Power Eng., Tampere Univ. of Technol., Finland
Volume
17
Issue
4
fYear
2002
fDate
10/1/2002 12:00:00 AM
Firstpage
951
Lastpage
956
Abstract
Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect aging and degradation of metal oxide material. The suitability of different methods for revealing internal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5-yr laboratory test series conducted for six different types of polymer-housed distribution class arresters. AC power losses, third-harmonic content of resistive leakage current, DC leakage current, and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with internal moisture are also studied. AC power loss and DC leakage current measurements were found to be good methods, whereas the other two can only be used as additional methods when diagnosing internal moisture in polymer-housed arresters.
Keywords
ageing; arresters; insulation testing; leakage currents; polymers; AC power loss; AC power losses; DC leakage current; aging; degradation; diagnostic methods; partial discharge measurement; polymer housed metal oxide surge arresters; polymer-housed distribution class arresters; resistive leakage current; Aging; Arresters; Degradation; Leakage current; Moisture measurement; Partial discharge measurement; Performance evaluation; Polymers; Surges; Testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.803694
Filename
1046868
Link To Document