DocumentCode
862789
Title
A time-domain procedure for locating switched capacitors in power distribution systems
Author
Kim, Jiseong ; Grady, W. Mack ; Arapostathis, Ari ; Soward, John C. ; Bhatt, Sid C.
Author_Institution
Dept. of Electr. & Comput. Eng., Texas Univ., Austin, TX, USA
Volume
17
Issue
4
fYear
2002
fDate
10/1/2002 12:00:00 AM
Firstpage
1044
Lastpage
1049
Abstract
This paper develops a method using transient voltage and current measurements at the substation to determine which capacitor in a multicapacitor feeder switched on to cause a measured transient. The procedure is based upon time-domain analysis where a backward Kalman filter estimates the initial voltage of all feeder capacitors, and those estimates indicate which capacitor switched. The result is an automated procedure that can help electric utilities determine if their capacitors are switching properly, and also help pinpoint the source of capacitor switching-related power-quality problems.
Keywords
Kalman filters; capacitor switching; distribution networks; power capacitors; power supply quality; power system parameter estimation; power system transients; substations; time-domain analysis; 25 kV; backward Kalman filter; discrete stochastic power system model; electric utilities; initial voltage estimation; multicapacitor feeder; power distribution systems; substation; switched capacitors location; time-domain analysis; time-domain procedure; transient; transient current measurements; transient voltage measurements; Noise measurement; Pollution measurement; Power capacitors; Power distribution; Power quality; Power system modeling; Substations; Time domain analysis; Vectors; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.805103
Filename
1046882
Link To Document