DocumentCode :
862789
Title :
A time-domain procedure for locating switched capacitors in power distribution systems
Author :
Kim, Jiseong ; Grady, W. Mack ; Arapostathis, Ari ; Soward, John C. ; Bhatt, Sid C.
Author_Institution :
Dept. of Electr. & Comput. Eng., Texas Univ., Austin, TX, USA
Volume :
17
Issue :
4
fYear :
2002
fDate :
10/1/2002 12:00:00 AM
Firstpage :
1044
Lastpage :
1049
Abstract :
This paper develops a method using transient voltage and current measurements at the substation to determine which capacitor in a multicapacitor feeder switched on to cause a measured transient. The procedure is based upon time-domain analysis where a backward Kalman filter estimates the initial voltage of all feeder capacitors, and those estimates indicate which capacitor switched. The result is an automated procedure that can help electric utilities determine if their capacitors are switching properly, and also help pinpoint the source of capacitor switching-related power-quality problems.
Keywords :
Kalman filters; capacitor switching; distribution networks; power capacitors; power supply quality; power system parameter estimation; power system transients; substations; time-domain analysis; 25 kV; backward Kalman filter; discrete stochastic power system model; electric utilities; initial voltage estimation; multicapacitor feeder; power distribution systems; substation; switched capacitors location; time-domain analysis; time-domain procedure; transient; transient current measurements; transient voltage measurements; Noise measurement; Pollution measurement; Power capacitors; Power distribution; Power quality; Power system modeling; Substations; Time domain analysis; Vectors; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2002.805103
Filename :
1046882
Link To Document :
بازگشت