Differential Protection Based on Zero-Sequence Voltages for Generator Stator Ground Fault
Author :
Nengling, Tai ; Stenzel, Juergen
Author_Institution :
Dept. of Electr. Eng., Shanghai Jiao Tong Univ.
Volume :
22
Issue :
1
fYear :
2007
Firstpage :
116
Lastpage :
121
Abstract :
This paper introduces a new differential protection scheme based on zero-sequence voltages with 100% coverage for generator stator ground faults. Analysis shows that the Delta-fundamental zero-sequence voltages and the Delta-third-harmonic voltages at the generator neutral and the terminals will change simultaneously, and they present some similar characteristics. According to that, the new scheme that exploits the fault information of both the zero-sequence fundamental voltage and the third-harmonic voltage is described. As it combines the information of the zero-sequence fundamental voltage and the third-harmonic voltage, the scheme can detect the ground fault with high sensitivity in 100% coverage winding. Simulation and field test results show that the proposed scheme can obtain higher sensitivity than the traditional schemes
Keywords :
electric generators; fault diagnosis; harmonic analysis; machine protection; stators; differential protection scheme; fault information; generator stator ground fault detection; third harmonic voltages; zero sequence voltage; Capacitance; Character generation; Fault detection; Hazards; Power generation; Protection; Protective relaying; Stator windings; Testing; Voltage; Fault contribution component; stator ground protection; third-harmonic voltage; zero-sequence fundamental voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.887099
Filename :
4039457
Link To Document :
بازگشت