DocumentCode
894598
Title
Performance of Power Differential Relay With Adaptive Setting for Line Protection
Author
Taalab, Abdel-Maksoud I. ; Darwish, Hatem A. ; Ahmed, Eman S.
Author_Institution
Fac. of Eng., El-Menoufia Univ., Shebin El-Kom
Volume
22
Issue
1
fYear
2007
Firstpage
50
Lastpage
58
Abstract
In this paper, proposed setting and response evaluations of power differential relay scheme for line protection are presented. Mathematical expressions describing the adaptive features of both active and reactive power settings are given. The union action of these two detectors is adopted to provide sensitive detection for high impedance internal faults and avoid maloperation for all power swings and external fault conditions. Response is computed for both active and reactive power detectors under different operation and fault conditions. The results corroborate the applicability and the immunity of the proposed relay scheme against the sampling misalignment and practical frequency drift. High sensitivity for high impedance internal faults is verified
Keywords
fault diagnosis; reactive power; relay protection; adaptive setting; fault detections; frequency drift; impedance internal faults; line protections; power differential relay; power swings; reactive power detection; response evaluation; Current transformers; Detectors; Fault detection; Frequency; Impedance; Power engineering and energy; Protection; Protective relaying; Reactive power; Sampling methods; Adaptive protection; high-impedance faults; line protection; power differential relay; relay setting;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.877101
Filename
4039480