DocumentCode
902691
Title
Generator works testing Sudden-short-circuit or standstill variable-frequency-response method
Author
Diggle, R. ; Dineley, J.L.
Author_Institution
University of Newcastle upon Tyne, Department of Electrical & Electronic Engineering, Newcastle upon Tyne, UK
Volume
128
Issue
4
fYear
1981
fDate
7/1/1981 12:00:00 AM
Firstpage
177
Lastpage
182
Abstract
The relative merits and shortcomings of sudden-short-circuit and standstill variable-frequency-response tests are discussed, and a computer simulation of line-switching tests on a 500 MW machine is used to compare the performance of equivalent circuits derived using the two methods
Keywords
AC generators; digital simulation; equivalent circuits; frequency response; machine testing; short-circuit currents; 500 MW machine; computer simulation; equivalent circuits; generator testing; line switching tests; standstill variable frequency response tests; sudden short circuit;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings C
Publisher
iet
ISSN
0143-7046
Type
jour
DOI
10.1049/ip-c.1981.0031