DocumentCode :
905996
Title :
Current interruption by disconnecting switch and earthing switch in GIS
Author :
Suzuki, K. ; Mizoguchi, H. ; Shimokawara, N. ; Murayama, V. ; Yanabu, S.
Author_Institution :
Toshiba Corporation, Heavy Apparatus Engineering Laboratory, High Power Laboratory, Kawasaki, Japan
Volume :
131
Issue :
2
fYear :
1984
fDate :
3/1/1984 12:00:00 AM
Firstpage :
54
Lastpage :
60
Abstract :
Disconnecting switches (DS) and earthing switches (ES) in gas insulated substations (GIS) can be required to interrupt high currents, which are closed-loop currents for DS and electromagnetic induced current for ES.DS and ES must also have full dielectric strength, even after interrupting these high currents many times. An investigation of the interrupting capability of five types of extinction chambers has revealed that magnetic driving types are optimum for closed-loop current interruption and suction types are optimum for electromagnetic induced current interruption because of their simple construction and excellent performance
Keywords :
earthing; switches; switching substations; GIS; closed loop; current interruption; disconnecting switch; earthing switch; electromagnetic induced; extinction chambers; gas insulated substations; interrupting capability;