DocumentCode :
915679
Title :
Design and installation of 500 V back-to-back shunt capacitor banks
Author :
Furumas, Brian C. ; Hasibar, Robert M.
Author_Institution :
Bonneville Power Adm., Portland, OR, USA
Volume :
7
Issue :
2
fYear :
1992
fDate :
4/1/1992 12:00:00 AM
Firstpage :
539
Lastpage :
545
Abstract :
The Bonneville Power Administration´s first 500 kV back-to-back shunt capacitor installation is described. The primary purpose of the capacitor banks is to support AC system voltage for transient stability following an outage of the HVDC Intertie line between Oregon and southern California. Design studies and equipment requirements are detailed in addition to electromagnetic transients program (EMTP) studies and subsequent field test results. Current-limiting reactors are used to limit inrush and outrush currents during capacitor switching
Keywords :
capacitor storage; power system interconnection; stability; transients; 500 kV; AC system voltage; Bonneville Power Administration; EMTP; HVDC Intertie line; Oregon; back-to-back shunt capacitor banks; current limiting reactors; electromagnetic transients program; inrush current limiting; outrush current limiting; southern California; transient stability; Capacitors; EMTP; Electromagnetic transients; HVDC transmission; Inductors; Shunt (electrical); Stability; Surges; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.127046
Filename :
127046
Link To Document :
بازگشت