DocumentCode
938575
Title
Transmission line distance protection based on wavelet transform
Author
Osman, A.H. ; Malik, O.P.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Calgary, Alta., Canada
Volume
19
Issue
2
fYear
2004
fDate
4/1/2004 12:00:00 AM
Firstpage
515
Lastpage
523
Abstract
Wavelet transform (WT) has the ability to decompose signals into different frequency bands using multiresolution analysis (MRA). It can be utilized in detecting faults and to estimate the phasors of the voltage and current signals, which are essential for transmission line distance protection. A digital distance-protection scheme for transmission lines based on analyzing the measured voltage and current signals at the relay location using WT with MRA is presented in this paper. The scheme has been tested by both computer simulation and experimentally. The tests presented include solid ground faults, phase faults, high impedance and nonlinear ground faults, and line charging.
Keywords
fault location; power engineering computing; power transmission faults; power transmission protection; transmission lines; wavelet transforms; current signal measurement; digital distance protection; fault detection; high impedance fault; line charging; multiresolution analysis; nonlinear ground fault; phase fault; signal decomposition; solid ground faults; transmission line distance protection; voltage measurement; wavelet transform; Fault detection; Frequency; Multiresolution analysis; Protection; Signal analysis; Testing; Transmission lines; Voltage; Wavelet analysis; Wavelet transforms;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.822531
Filename
1278403
Link To Document