• DocumentCode
    943909
  • Title

    Switching-impulse strength of the external insulation of three-phase power transformers

  • Author

    Studinger, H. ; Weck, K.-H.

  • Author_Institution
    Forschungs Gemeinschaft f¿¿r Hochspannungs und Hochstromtechnik EV, Mannheim, West Germany
  • Volume
    133
  • Issue
    8
  • fYear
    1986
  • fDate
    11/1/1986 12:00:00 AM
  • Firstpage
    534
  • Lastpage
    542
  • Abstract
    The switching-impulse strength phase-to-phase and phase-to-earth has been investigated on a power transformer dummy to provide data for the design of its external clearances. The dummy was equipped with 420 kV bushings, but also simulations were used to obtain smaller or larger distances to earth. The clearances were varied between 2 m and 6 m. The influence of rain is included. The report offers design curves for power transformer clearances covering the range of rated switching-impulse withstand voltages up to 1550 kV, phase-to-earth, and up 2400 kV, phase-to-phase.
  • Keywords
    electric strength; high-voltage techniques; insulation testing; power transformers; transformer testing; 1550 kV; 2 m to 6 m clearance; 2 to 6 m; 2400 kV; 420 kV; 420 kV bushings; design; external clearances; rain; three-phase power transformers; up 2400 kV; up to 1550 kV;
  • fLanguage
    English
  • Journal_Title
    Physical Science, Measurement and Instrumentation, Management and Education - Reviews, IEE Proceedings A
  • Publisher
    iet
  • ISSN
    0143-702X
  • Type

    jour

  • DOI
    10.1049/ip-a-1.1986.0071
  • Filename
    4647849