• DocumentCode
    965621
  • Title

    Novel approach to reducing the inrush current of a power transformer

  • Author

    Cheng, C.-K. ; Liang, T.-J. ; Chen, J.-F. ; Chen, S.-D. ; Yang, W.-H.

  • Author_Institution
    Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
  • Volume
    151
  • Issue
    3
  • fYear
    2004
  • fDate
    5/8/2004 12:00:00 AM
  • Firstpage
    289
  • Lastpage
    295
  • Abstract
    An inrush current is a transient current that results from a sudden change in the exciting voltage across a transformer´s windings. It may cause inadvertent operation of the protective relay system and necessitate strengthening of the transformer´s mechanical structure. A novel approach to reducing the inrush current of power transformer, by increasing the transient inductance of the primary coil by changing the distribution of the coil winding is presented. During the period of this study, 30 patterns of 220 V/110-220 V 5 kVA-power transformers with three-layer and four-layer winding structures were developed as demonstrations of the approach. According to field tests and theory, the proposed method successfully limits the inrush current.
  • Keywords
    overcurrent protection; power transformer protection; relay protection; transformer windings; transients; 220 to 110 V; 5 kVA; inrush current reduction; power transformer; protective relay system; transformer winding; transient current; transient inductance;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2352
  • Type

    jour

  • DOI
    10.1049/ip-epa:20040223
  • Filename