• DocumentCode
    973048
  • Title

    Modeling and analysis of unsymmetrical transformer banks serving unbalanced loads

  • Author

    Kersting, William H. ; Phillips, W. Howard

  • Author_Institution
    Coll. of Eng., New Mexico State Univ., Las Cruces, NM, USA
  • Volume
    32
  • Issue
    3
  • fYear
    1996
  • Firstpage
    720
  • Lastpage
    725
  • Abstract
    It is a common practice to serve combination three-phase and single-phase loads from an unsymmetrical three-phase transformer bank and a four-wire secondary. Depending upon the loads and company standards, nine different transformer connections can be considered along with either an open four wire or a quadraplex secondary. The selection of the proper connection and transformer ratings can he achieved by the correct modeling and analysis of a system consisting of an equivalent source, transformer bank, secondary, and loads. This paper develops the models for the nine transformer connections, the secondary, and the loads. A computer program has been written that allows the analysis of the system for loading and short-circuit studies. The paper includes several examples of different normal and abnormal operating conditions on some of the transformer connections
  • Keywords
    power transformers; short-circuit currents; abnormal operating conditions; computer program; equivalent source; four-wire secondary; normal operating conditions; quadraplex secondary; single-phase loads; three-phase loads; transformer connections; transformer ratings; unbalanced loads; unsymmetrical transformer banks; Impedance; Industry Applications Society; Phase transformers; Power engineering and energy; Power engineering computing; Power system modeling; Power transformers; Voltage; Wire;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.502187
  • Filename
    502187