DocumentCode
976094
Title
Performance of station service induction motors following full load rejection of a nuclear generating unit
Author
Rogers, G.J. ; Beaulieu, R.E. ; Hajagos, L.M.
Author_Institution
Ontario Hydro, Ont., Canada
Volume
10
Issue
3
fYear
1995
fDate
8/1/1995 12:00:00 AM
Firstpage
1314
Lastpage
1320
Abstract
In this paper we describe simulations, using EPRI´s Extended Transient Midterm Stability Program (ETMSP), which were performed to understand the nature of a failed load rejection test on a nuclear unit. The failure was a result of large induction motors stalling, causing protective relays to operate. Potential remedial measures were simulated and a final solution, using a temporary voltage boost on the AVR, adopted and implemented to prevent further failures
Keywords
digital simulation; induction motors; nuclear power stations; power engineering computing; power station load; simulation; stability; transient analysis; voltage control; voltage regulators; EPRI; Extended Transient Midterm Stability Program; automatic voltage regulator; excitation system; failed load rejection test; full load rejection; induction motor stalling; nuclear generating unit; protective relays; station service loads; temporary voltage boost; turbine governor; Control systems; Induction generators; Induction motors; Inductors; Nuclear power generation; Performance evaluation; Protection; Protective relaying; Testing; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.466522
Filename
466522
Link To Document