• DocumentCode
    978704
  • Title

    Conductor qualification tests for the 30-MJ Bonneville Power Administration SMES coil

  • Author

    Schermer, R.I. ; Boenig, H.J. ; Henke, M. ; Turner, R.D. ; Schramm, R.

  • Author_Institution
    Los Alamos National Laboratory, Los Alamos, NM
  • Volume
    17
  • Issue
    1
  • fYear
    1981
  • fDate
    1/1/1981 12:00:00 AM
  • Firstpage
    356
  • Lastpage
    359
  • Abstract
    The 30-MJ energy storage coil for the Bonneville Power Administration requires a low-loss, cryostable conductor that is able to carry 4.9 kA in a field of 2.8 T and will maintain its properties over 108partial discharge cycles. The multi-level cable which satisfies these requirements has been extensively tested at various stages in its development and in its final form. Tests have been performed to determine the effect of manufacturing options on ac losses, low temperature electrical resistivity, stability, and fatigue resistance of the insulated conductor. This paper will concentrate on the stability and fatigue tests which have not previously been reported.
  • Keywords
    Power generation peaking capacity; Superconducting magnets, energy storage; Coils; Conductors; Electric resistance; Energy storage; Fatigue; Partial discharges; Qualifications; Samarium; Stability; Testing;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.1981.1060973
  • Filename
    1060973