DocumentCode
985395
Title
Performance of distance relays on shunt-FACTS compensated transmission lines
Author
Sidhu, Tarlochan Singh ; Varma, Rajiv K. ; Gangadharan, Pradeep Kumar ; Albasri, Fadhel Abbas ; Ortiz, German Rosas
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Western Ontario, London, Ont., Canada
Volume
20
Issue
3
fYear
2005
fDate
7/1/2005 12:00:00 AM
Firstpage
1837
Lastpage
1845
Abstract
This paper presents a study of the performance of distance protection relays when applied to protect shunt Flexible AC Transmission System (FACTS) compensated transmission lines. The objective of this study is to evaluate the performance of distance relays on transmission lines with FACTS devices applied for mid point voltage control. Effect of two types of shunt FACTS devices, Static Var Compensators (SVC) and Static Synchronous Compensators (STATCOM) are studied. The study is conducted in three stages. First the situation is studied analytically, where the errors introduced in the impedance measurement due to the presence of shunt FACTS devices on the line are analyzed. In the second stage, the situation is simulated using transient simulation software, EMTDC. In this method, the response of FACTS devices for different fault conditions and system conditions is also modeled. This method brings out some unique problems that would be experienced by the distance relays due to some specific characteristics of the FACTS devices. Finally, the findings are confirmed by testing a commercial distance relay using a Real Time Digital Simulator (RTDS). The results obtained by testing the commercial relay validate the analytical and simulation studies.
Keywords
flexible AC transmission systems; power engineering computing; power system transients; power transmission faults; power transmission lines; power transmission protection; relay protection; static VAr compensators; voltage control; STATCOM; distance protection relays; fault condition; flexible AC transmission system; real time digital simulator; shunt FACTS compensated transmission lines; static Var compensators; static synchronous compensators; transient simulation software; voltage control; Automatic voltage control; Error analysis; Flexible AC transmission systems; Impedance measurement; Protection; Protective relaying; Static VAr compensators; Testing; Transmission lines; Voltage control; Distance protection relay; flexible ac transmission system (FACTS); power system protection; real-time digital simulator (RTDS); shunt compensation; static synchronous compensators (STATCOM); static var compensators (SVC);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2005.848641
Filename
1458851
Link To Document