• DocumentCode
    998201
  • Title

    EMTP transient modeling of a distance relay and a comparison with EMTP laboratory testing

  • Author

    Wilson, Robert E. ; Nordstrom, Jerry M.

  • Author_Institution
    Idaho Univ., Moscow, ID, USA
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    984
  • Lastpage
    992
  • Abstract
    A method to test the transient performance of a sampled-data relay is given. A model of one measuring unit of a digital relay is created on a personal computer. The simulations are compared with laboratory results obtained by applying digitally generated waveforms to the actual relay. Computer modeling of the digital relay is done within the models version of the Transient Analysis of Control System (TACS) subsection of the ElectroMagnetics Transient Program (EMTP). The input filter, analog-to-digital converter, Fourier fundamental frequency detector, and the relay measuring principle of one digital microprocessor-based relay are modeled. An actual 115 kV 150 mile long transmission line is simulated using the EMTP.<>
  • Keywords
    analogue-digital conversion; automatic test equipment; automatic testing; digital simulation; laboratories; microcomputer applications; power system analysis computing; power system protection; power transmission lines; relay protection; software packages; 115 kV; 150 miles; EMTP; ElectroMagnetics Transient Program; Fourier fundamental frequency detector; TACS; Transient Analysis of Control System; analog-to-digital converter; computerised instrumentation; digital simulation; distance relay; input filter; laboratory testing; microprocessors; personal computer; power system analysis computing; relay protection; transient modeling; transmission line;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252626
  • Filename
    252626